To confirm the delivery cost before placing your order, please email us at [email protected] .
Up to 10-15 kg per parcel


TOP SANTEHNIKA.LV official dealer:


* ESTO only in Estonia, Latvia, Lithuania
HERZ PUMPFIX MIX heating circuit unit without pump DN25, Kvs 10.0, 1451108

HERZ PUMPFIX MIX heating circuit pump group without pump DN25, Kvs 10, 1451108
HERZ PUMPFIX MIX 1451108 is a factory-preassembled DN25 heating circuit mixing group without a circulation pump. It is designed for heating circuits that require control of the supply temperature by mixing hotter supply water with cooler return water. Its compact construction saves installation time and space in boiler rooms and heating installations.
The assembly includes a three-way mixing valve with a Kvs value of 10 m³/h and an electric 230 V actuator operated by a three-point control signal. The actuator has a full operating time of 140 seconds. When connected to a suitable heating controller, the mixing valve allows the heating circuit supply temperature to be adjusted to system requirements.
The supply and return lines feature isolating ball valves with thermometers integrated into their handles. Red markings identify the supply line, while blue markings indicate the return line. The assembly also includes a non-return valve, a bypass valve and preassembled pipe connections that simplify integration into the heating circuit.
The group is designed for a circulation pump with an installation length of 180 mm, which must be purchased and installed separately. The centre distance between the supply and return connections is 125 mm. The included thermal insulation housing helps reduce heat loss while ensuring a compact and organised installation.
HERZ PUMPFIX MIX DN25 is suitable for a maximum heating medium temperature of 110 °C and an operating pressure of up to 10 bar. The integrated thermometers have a measurement range of 0–120 °C. The group is suitable for boiler and heating manifold installations and must be installed in accordance with the manufacturer's hydraulic connection and electrical control requirements.
Technical information
| General information | |
| Manufacturer | HERZ |
| Series | PUMPFIX MIX |
| Product type | Heating circuit mixing group without pump |
| Manufacturer code | 1 4511 08 / 1451108 |
| EAN | 3838963423010 |
| Technical specifications and equipment | |
| Nominal diameter | DN25 |
| Flow coefficient Kvs | 10 m³/h |
| Mixing valve | Three-way, electric actuator |
| Actuator power supply | 230 V |
| Actuator control | Three-point |
| Actuator running time | 140 seconds |
| Pump installation length | 180 mm |
| Circulation pump | Not included |
| Supply/return centre distance | 125 mm |
| Isolating valves | Ball valves with integrated thermometers |
| Non-return valve | Included |
| Bypass valve | Included |
| Thermometer range | 0–120 °C |
| Maximum operating temperature | 110 °C |
| Maximum operating pressure | 10 bar |
| Upper connections | G 1", female thread |
| Lower connections | G 1 1/4", male thread |
| Thermal insulation | Insulation housing included |
| Installation position | Vertical, wall or heating manifold |
- Select the circulation pump separately according to the hydraulic requirements of the system.
- Have the actuator connection and heating control configuration carried out by a qualified specialist.
- Before installation or maintenance, isolate the heating system and make sure it is depressurised.
- Follow the HERZ installation instructions and permissible operating conditions.
Suitable for this product :