To confirm the delivery cost before placing your order, please email us at [email protected] .
Up to 10-15 kg per parcel


TOP SANTEHNIKA.LV official dealer:


* ESTO only in Estonia, Latvia, Lithuania
MIDEA MULTISPLIT INVERTER outdoor unit 12.3 / 12.3 kW, for 5 indoor units, R32, M5OE-42HFN8-Q

MIDEA MULTISPLIT INVERTER Outdoor Unit 12.3/12.3 kW, for 5 Indoor Units, R32, M5OE-42HFN8-Q
MIDEA M5OE-42HFN8-Q is a powerful inverter Multi-Split air-conditioning outdoor unit designed for connection of up to five compatible indoor units. A single outdoor unit can provide cooling and heating for several rooms while reducing the number of outdoor units required on the building facade.
Nominal cooling capacity is 12.30 kW and nominal heating capacity is also 12.30 kW. Inverter control automatically adjusts compressor operation according to actual demand, providing more stable room temperatures and efficient energy use.
Nominal electrical input is approximately 3.83 kW in cooling and 3.30 kW in heating. The manufacturer specifies an EER of 3.21 and a COP of 3.71.
The outdoor unit uses R32 refrigerant with a factory charge of 2.40 kg. It provides five 1/4" liquid connections, four 3/8" gas connections and one 1/2" gas connection.
Maximum total refrigerant piping length is 80 m, while the maximum length of one branch is 35 m. Maximum height difference between outdoor and indoor units is up to 15 m, while up to 10 m is permitted between indoor units.
The M5OE-42HFN8-Q is designed for both cooling and heating and uses a 220–240 V / single-phase / 50 Hz power supply. This product is the outdoor unit only; compatible MIDEA Multi-Split indoor units and professional installation are required for a complete system.
Technical information
| Basic information | |
| Manufacturer | MIDEA |
| Model | M5OE-42HFN8-Q |
| System type | Multi-Split Inverter outdoor unit |
| Maximum indoor units | 5 |
| EAN | 8033638102435 |
| Cooling and heating | |
| Nominal cooling capacity | 12.30 kW |
| Cooling capacity range | 2.05–14.15 kW |
| Nominal heating capacity | 12.30 kW |
| Heating capacity range | 2.34–14.80 kW |
| Nominal input – cooling | 3.83 kW |
| Nominal input – heating | 3.30 kW |
| EER / COP | 3.21 / 3.71 |
| Refrigerant circuit | |
| Refrigerant | R32 |
| Factory charge | 2.40 kg |
| Liquid connections | 5 × 1/4" |
| Gas connections | 4 × 3/8" + 1 × 1/2" |
| Max. total piping length | 80 m |
| Max. individual branch length | 35 m |
| Max. height difference ODU–IDU | 15 m |
| Max. height difference IDU–IDU | 10 m |
| Electrical and physical data | |
| Power supply | 220–240 V / 1 phase / 50 Hz |
| Maximum input power | 4700 W |
| Maximum current | 20.5 A |
| Recommended protection | 25 A |
| Dimensions (W×H×D) | 946 × 810 × 410 mm |
| Net weight | 73.3 kg |
| Sound pressure level | 62 dB(A) |
| Sound power level | 68 dB(A) |
| Cooling operating range | −15 to +50 °C |
| Heating operating range | −15 to +24 °C |